品牌:ASCO | 型号:8210G002 | 材质:黄铜,不锈钢 |
类型(通道位置):先导式 | 连接形式:螺纹 |
ASCO电磁阀8210G087 SC8210G087 EF8210G087 ASCO电磁阀8210G094 SC8210G094 EF8210G094 ASCO电磁阀8210G037 SC8210G037 EF8210G037 ASCO电磁阀8210G015 SC8210G015 EF8210G015 ASCO电磁阀8210G006 SC8210G006 EF8210G006 ASCO电磁阀8210G001 SC8210G001 EF8210G001 ASCO电磁阀8210G093 SC8210G093 EF8210G093 ASCO电磁阀8210G036 SC8210G036 EF8210G036 ASCO电磁阀8210G073 SC8210G073 EF8210G073
ASCO防爆电磁阀 ASCO隔爆电磁阀 ASCO本安型防爆电磁阀 ASCO脉冲除尘阀优势供应
武汉华哲嘉业自动化设备有限公司
联系人:刘工
手机:159 2707 8030
电话:027-8727 9388
传真:027-8727 9088
QQ:445279690
ASCO所有产品按照***设计和生产,ASCO电磁阀产品可满足各种应用的需要,控制不同液态及气态流体,并提供广泛的选择:其介质可以是易燃、易爆或腐蚀性的;压力可达到150巴;温度可以从-50C到300C;口径从1/8英寸至6英寸,ASCO电磁阀包括普通型、防爆型、手动复位、本安型、滑动式、长寿型、蒸汽/热水专用及气控阀。ASCO电磁阀***防爆性能广泛应用于石化、电厂等行业。同时,根据不同的产品也适用于其他行业如:环保和水处理以及医疗设备仪器等相关OEM配套等等ASCO旗下各种电磁阀,具体大的类型有:
1。2位2通通用型阀。(8210系列,8262/8263系列,238系列(欧洲产品),106系列,107系列.)
2。热水/蒸汽阀。(2位2通热水/蒸汽系列,E290系列,8315蒸汽系列。)
3。2位3通阀。(8316系列,先导式;8320系列,直动式。)
4。2位4通阀。(8342系列,直动式;8344系列,先导式;8345系列,先导紧凑型。)
5。2位5通阀。(551系列)
6。本安型防爆电磁阀。(2位2通阀,2位3通阀,2位4通阀。)
7。低功耗电磁阀。(2位2通阀,2位3通阀,2位4通阀。)
8。手动复位电磁阀。(8015/8025系列;8037/8308,8310系列;8327系列,8047/8408/8410系列。)
9。精密微型阀。(AL/AM系列;458系列;通用型阀;190&330系列;隔离型阀;S系列,夹紧阀)
10。阀位指示器。(VR7系列。)
11。脉冲电磁阀及相关元件。(其中:353系列,110系列,908系列,435/450系列,342系列,NF、PVT系列,EM、EF系列等产品现已在除尘与环保行业得到了广泛应用。)
SCG551A005MS,SCG551A001MS,SCG551A002MS,EFG551H401MO,EFG551A001MS,
SCG353A043,SCG353A044,SCG353A047,SCG353A051,EF8314G301,SCG531D001MS,8320G174,EF8320G174,EF8320G176,8320G184, EF8320G184,8320G186,EF8320G186,EF8320G203,EF8320G203V,EF8314G054,8320G200,EF8320G200,NF8327B102,WSNF8327B102,EF8551A001MS,EF8551G401MO,EFG551A002MS,WBIS8551A301,SCG551A002MS,SCG551D001MS,NF8327B002,SCG531A018,WBIS8314A301,NF8327B012,WSNF8327B112,WSNF8327B002,WSNF8551A321,NF8551A422,SCXE353.060,SCXE238A002,EFG551H417,VCEFCMG551H301,SCG353.051,
VCEFG551H417,400425-117,400325-117,238610-058-D,238610-158-D,400325-642,400425-342,EFG353A044,EFG353A047,SCG353A050,SCXE353.60,C113444, C113827,C113685,C113686,C123432,C123433,SCG553A017MS,8210G002,
8210G009,VCEFG551H401MO,43004886-025,
DESCRIPTION
Series 8210 valves are 2-way normally closed, internal pilot
operated solenoid valves designed for general service. Valves are
made of rugged forged brass. Series 8210 valves are provided with
a general purpose solenoid enclosure.
Series EF8210 and 8211 are the same as Series 8210 valves except
that they are provided with an explosionproof/watertight solenoid
enclosure.
Notice: These valves are not certi? ed as lead-free under the
Safe Water Drinking Act SWDA 1417 and are not intended
for use on drinking water systems. They are intended for
control of water in industrial applications. Consult ASCO
for valves rated for use in potable water applications.
OPERATION
Normally Closed: Valve is closed when solenoid is de-energized;
open when energized.
Note: No minimum operating pressure differential required.
Manual Operator (Optional)
Manual operator allows manual operation when desired or during an
interruption of electrical power.
? For 3/4” NPT Valve Construction
To engage manual operator (open valve), rotate stem clockwise
as far as possible. Valve will now be in the same position as
when the solenoid is energized. To disengage manual operator,
rotate manual operator counterclockwise as far as possible
before operating electrically.
? For 1” NPT Valve Construction
To engage manual operator (open valve), push knobs upward
and rotate one quarter turn. Valve will now be in the same
position as when the solenoid is energized. To disengage
manual operator, rotate manual operator counterclockwise one
quarter turn until the manual operator returns to its original
position before operating electrically.
INSTALLATION
Check nameplate for correct catalog number, pressure, voltage,
frequency, and service. Never apply incompatible ? uids or exceed
pressure rating of the valve. Installation and valve maintenance to
be performed by quali? ed personnel.
Future Service Considerations
Provision should be made for performing seat leakage, external
leakage, and operational tests on the valve with a nonhazardous,
noncombustible ? uid after disassembly and reassembly.
Positioning
This valve is designed to perform properly when mounted in any
position. However, for optimum life and performance, the solenoid
should be mounted vertically and upright to reduce the possibility
of foreign matter accumulating in the solenoid base sub-assembly
area.
Piping
Connect piping to valve according to markings on valve body.
Apply pipe compound or PTFE tape sparingly to male pipe threads
only. If applied to valve threads, the compound may enter the valve
and cause operational dif? culty. Avoid pipe strain by properly
supporting and aligning piping. When tightening the pipe, do not
use valve or solenoid as a lever. Locate wrenches applied to valve
body or piping as close as possible to connection point.
CAUTION: To protect the solenoid valve, install a strainer
or ? lter suitable for the service involved in the inlet side
as close to the valve as possible. Clean periodically
depending on service conditions. See ASCO Series 8600
and 8601 for strainers.
MAINTENANCE
WARNING: To prevent the possibility of severe
personal injury or property damage, turn off
electrical power, depressurize valve, extinguish
all open ? ames, and avoid any type of sparking
or ignition. Vent hazardous or combustible ? uid
to a safe area before servicing the valve.
NOTE: It is not necessary to remove the valve from the pipeline for
repairs.